Welcome to our website
  • Mobile
  • 01028993434
  • Address
  • The Industrial Zone, New Cairo
  • Mail Us
  • Kenana@kenanaeg.com

Differential pressure transmitter - FKC

Differential pressure transmitter - FKC
Can We Help You ?

If you need any assistance, please feel free to contact us.

Contact Us
Differential pressure transmitter - FKC

The FCX-AIV family of FKC pressure transmitters precisely measures differential pressure, liquid level or flow, and converts it into a directly proportional 4-20 mA output signal. At the heart of the measuring element is a micro-capacitive silicon transducer with a proven track record in the process industry. The digital signal processing carried out by the electronics unit ensures outstanding accuracy and stability. The FCX-AIV family of pressure transmitters complies with integrity and safety levels SIL 2 (HFT=0) and SIL 3 (HFT=1) in accordance with IEC 61508 and IEC 61511 standards.

 

Housing L- or T-shaped housing
Measuring ranges (kPa) [e.max.] 1
6
32
130
500
3000
20000
Weight per kg (without indicator) 3,1
Accuracy ± 0.065% of the measurement range set as standard.
An accuracy of ±0.04% is also available as an option.
Materials in contact with the process Stainless steel 316 L, Hastelloy-C, Monel, Tantalue, Stainless steel 316 L + Gilding, Monel coating, Tantalue coating
Case materials Low-copper aluminum alloy with polyester coating, or 316 L stainless steel
Membrane materials Stainless steel 316 L
Hastelloy-C
Monel
Tantalum
Stainless steel 316 L and Gilding
Gilding and Ceramics
Stability ±0.1% of maximum scale for 10 years for digit
6 = 3, 5, 6, 8 and 9.
Elevation / Deletion From -100 to +100% of maximum scale
Scale setting range 1 to 1/100 of maximum scale
Measurement cycle 40 ms
Communication protocol HARTTM 7 communication protocol
Process temperature From +40° to +120°C (versions for higher temperatures are available)
Ambient temperature From -40° to +85 °C
Power supply 10.5 to 45 V DC
Output signal / Load resistance 4-20 mA / 250 Ω typical
Damping Configurable between 0.04 and 32 secs
Zero and span adjustment Via external sensor screw, local three-button display or HARTTM protocol
Electrical connections M20x1.5" / 1/2 - 14 NPT / Pg13.5
Options Digital indicator, degreasing treatment, oxygen service, chlorine service, additional stainless steel identification plate